Commercial electrical inspection and thermal survey in Glasgow
A commercial catering unit in Glasgow was having repeated problems with its electrical accessories
The job
A commercial catering unit in Glasgow was having repeated problems with its electrical accessories. Sockets were burning out, outlets were failing and the unit was losing power during its busiest service periods. The customer needed to know why the accessories kept failing under kitchen load, rather than simply replacing them again and hoping for a better result. We were asked to carry out a full live electrical load assessment and a thermal imaging survey to diagnose the cause.
What we did
We tested the live circuit currents with a calibrated clamp meter and a multifunction tester, then scanned the distribution board, terminals and supply tails with a Hikmicro thermal imaging camera while the kitchen was running under full load. The testing showed a peak demand of around 129A drawing through 16mm² tails on a 100A single-phase board. The thermal scans picked up severe hotspots on the incoming terminals, with heat building within two minutes of full kitchen operation. Commercial catering equipment was being run through domestic 13A outlets, which was causing thermal degradation of the accessories and an immediate fire risk. We compiled a formal technical report with the thermal photo evidence and our recommendations: an urgent commercial 3-phase supply upgrade to balance the roughly 129A kitchen load safely across three phases, bringing it down to around 43A per phase, and heavy-duty 16A and 32A commando outlets in place of the domestic sockets, so the equipment runs on accessories rated for continuous commercial use.
Challenges
There was no access to the main plant room, so all of the testing and thermal diagnostic work had to be carried out precisely at the unit's own distribution board, under live conditions with a commercial kitchen in full operation.
The result
The inspection took half a day on site, plus the time to complete the technical write-up. The customer now has clear, evidence-backed documentation showing that the supply infrastructure is overloaded, along with a plain route to putting it right. The thermal imaging was the key part of this job: this kind of heat stress is not visible to the eye, and without the camera the problem could easily have gone unidentified until something failed properly.
Our Work
Planning a Commercial electrical inspection and thermal imaging survey?
Call us on 07493 053049 for a free quote in Glasgow and the surrounding areas.